4
 
 

Panel Air Conditioners

The electrical / electronic components used in control panels of different applications dissipate heat continuously. Also these panels are operating round-o-clock and round the year at any location. The life of electronic components reduces drastically if exposed to high temperatures for long period. Normally, a temperature of 27 Deg. Celsius with 45-50% relative humidity is considered ideal for maximum life of switches and other components. Hence reliable air-conditioning is required to remove the heat for sustained functioning of these panels.
 

PANCOL offered by NEW ANUCOOL ENGINEERS is highly energy efficient, light weight, “Fit and forget” series of standard Panel Air conditioners ranging from 250 W upto 3500 W with customized solutions as well.

 
Features
High quality CRCA / SS 304 Powder coated body
100 % tested for performance on specially designed Test Rig simulated for on-site load conditions
Closed loop design to keep hostile industrial environment out of panel. No dust, no fumes, no danger to the inside electronics
Operating on environmental friendly 134a refrigerant, which is an approved refrigerant under Montreal protocol. 134a is having zero (ODP) Ozone Depletion Potential.
Emerson or equivalent made compressors with high reliability
Microprocessor based  Digital Two set point Temperature indicator cum Controller (TIC)
Potential free alarm for high and low temperature alerts ( Optional )
High / Low pressure cut-off switches
Lubrication free sealed ball bearing motors
 
Pancol Mounting Arrangement

The choice of mounting depends obviously upon the space available for fitment on panel. We offer air conditioners in side mounting, top mounting and stand alone type to suit any type of panel.
 
1) SIDE MOUNTED Control panels where there is an unrestricted flow of air from one end to other end this type is preferred, so as to ensure uniform cooling of panel. These panels are mounted either on the doors or sidewalls of control panels.

2) STAND ALONE TYPE The use of side mounted or top mounted panels is not suitable in some cases like for cooling of partitioned panels, where this arrangement is preferred.

3) TOP MOUNTED This type is preferred when side mounting or stand-alone type is not suitable. This Panel AC is mounted on roof of the control panel.

 

Advantages of Pancol Over Standard Room Air Conditioners :

 
1)  High SHF:- For panels, due to no occupancy and no positive fresh air
Intake, the latent heat component is almost negligible, resulting in nearly unity sensible heat factor. Thus the dehumidified air quantity required will be much higher than that available in a room air conditioner of equivalent capacity.

2) Bigger Evaporator Coil and Evaporator Fan: - To remove the high sensible
heat load effectively, both the evaporator fan and evaporator coil need to be
substantially oversized compared to room air conditioners. This increases the first cost of panel air conditioners compared to room air conditioners.

3) High Energy Efficiency Ratio: - Due to bigger evaporator coils, panel ACs
operate at much higher suction temperature (approx. 6 to 7oC than room ACs) Thus EER is improved. Generally energy saving due to Panel ACs is about 25%

4) Reliability: - High priority is assigned during design and testing of Panel ACs to achieve a higher MTBF (Mean Time between Failures)

5) Continuous Duty operation: - Standard room ACs is designed to run 8 to 10 hours a day whereas Panel AC is designed for continuous duty operation round the clock, round the year,
 

Pancol Applications

  1. Power generation
  2. Chemical plants
  3. Process automation
  4. Steel Plants
  5. CNC Machine Tools
  6. Textile machines
  7. Food processing machinery
  8. Telecom
Panel Air Conditioners
Request Quote
 
Panel Technical Spcecification
 
   

STANDARD MODELS

REFRIGERANT

COOLING CAPACITY

RATED

OVERALL SIZE WxHxD
MM

WEIGHT IN
KG

WATTS

KCAL/HR

POWER (W)

CURRENT
(A)

VOLTAGE (V)

PANCOL-250-S-AX
R 134a
250
214
150
1.4
230
370 x 540 x 180
27
PANCOL-500-S-AX
R 134a
500
428
350
2.5
230
300 x 525 x 270
38
PANCOL-600-S-CE
R 134a
600
514
440
2.5
230
310 x 810 x 260
43
PANCOL-1000-S-CE
R 134a
1000
857
585
2.7
230
375 x 950 x 230
49
PANCOL-1000-S-CE-1
R 134a
1000
857
595
2.7
230
395 x 710 x 255
63
PANCOL-1500-S-CE
R 134a
1500
1285
875
4.7
230
480 x 982 x 300
65
PANCOL-2000-S-CE
R22
2000
1712
1280
6.0
230
440 x 982 x 300
70
 
NOTE: Design specifications and technical characteristics are subject to change without notice.
 
   
 
   
Water Chiller | Printing Chiller | Educational Test Rig | Refrigeration Test Rig | Air Conditioning Test Rig | Water Cooler Test Rig | Ice Plant Test Rig | Mechanical Heat Pump Test Rig | Computerised Heat Pump Test Rig | Vapour Absorption Test Rig | Cascade System Test Rig | Vortex Tube Test Rig | Cut-Section Models Of Various Compressors | Display Board Containing Various Controls & Components Used In Rac | Oil Cooler - Oil Chiller | Sample Gas Coolers | Panel Air Conditioners